The CSP-series consists of a number of surge protection devices for the protection of coaxial RF-cables.
CSP-series protection devices can be installed as feed-through components directly into a bulkhead such as the wall of a shielded room. This diverts surge currents on the outer conductor to the grounded shield. Overvoltage surges on the inner conductor are limited with respect to the outer conductor.
Depending on the application different protection technologies with varying protection levels are used. The transient residual let-through energy strongly depends on the protection technology and the temporal behaviour of the overvoltage surge. Therefore standardized pulse shapes and a load impedance matched to line impedance are used for specification.
GDT-technology (Gas Discharge Tube) has the advantage of broadband and extremely low insertion loss protection from DC (e.g. for remote powering of an external antenna) up to several GHz. The protection levels are limited due to the large bandwidth and are mostly determined by the behaviour of the gas discharge tube.
Stubline technology, also called lambda/quater or quater wave technology, works like a bandpass filter for a certain passband. Advantages are low attenuation in the passband and high surge current capability.
Highpass filter technology blocks low frequencies while having low insertion loss in the passband. This permits relatively low transient residual energies. Special versions additionally permit DC-feed-through for remote powering over the coaxial cable.
CSP-40101 protects a coaxial cable with N-connectors using gas discharge tube technology. Frequencies from DC to 1 GHz and RF power up to 150W pass almost unchanged, overvoltages are short-circuited to the outer conductor by a powerful gas tube arrester. CSP-40101 datasheet
CSP-40102 protects a coaxial cable with BNC-connectors using gas discharge tube technology. Frequencies from DC to 1 GHz and RF power up to 150W pass almost unchanged, overvoltages are short-circuited to the outer conductor by a powerful gas tube arrester. CSP-40102 datasheet
CSP-43101 protects a coaxial cable with N-connectors using gas discharge tube technology. Frequencies from DC to 1 GHz and RF power up to 300W pass almost unchanged, overvoltages are short-circuited to the outer conductor by a powerful gas tube arrester. CSP-43101 datasheet
CSP-40101 protects a coaxial cable with N-connectors using gas discharge tube technol7gy. Frequencies from DC to 1 GHz an RF power up to 700W pass almost unchanged, overvoltages are short-circuited to the outer conductor by a powerful gas tube arrester. CSP-47101 datasheet
CSP-55101 protects a coaxial cable with N-connectors using high-pass filter technology. Frequencies from 806 to 2500 MHz and RF power up to 500W pass almost unchanged, DC and low frequencies are blocked. This also blocks most of the energy of transient overvoltages resulting in very good protection levels. CSP-55101 datasheet
CSP-73101 protects a coaxial cable with N-connectors using stubline technology. Frequencies from 2000 MHz to 6000 MHz and RF power up to 300W pass almost unchanged, DC and low frequencies are blocked. This also blocks most of the energy of transient overvoltages resulting in very good protection levels. CSP-73101 datasheet
CSP-81101 protects a coaxial cable with N-connectors using hybrid gas discharge tube and filter technology. Frequencies from 650 MHz to 2500 MHz and RF power up to 50W pass almost unchanged, additionally CSP-81101 passes DC voltages up to 15V and currents up to 3A. This permits use for remote powering, e.g. for an antenna amplifier. A typical application is an active GPS-antenna. CSP-81101 datasheet
The PLP-Series consists of highly effective EMP Surge Protection Filter Devices (SPD's) for NEMP / HEMP / EMP protection as well as for lightning surge protection according to IEC class I+II+III.PLP-series SPD's are surge protection filters designed for feed-through installation into a bulkhead such as the metallic wall of a shielded room. This makes PLP-series SPD's to work simultaneously as protection against transient overvoltage surges as well as an excellent EMC-solution against conducted high frequency disturbances.
PLP-Series products are threat-level HEMP-tested according to MIL-STD-188-125. Additonally the PLP-series is approved against the mechanical shock of a 3 bar blast according to Swiss Federal Office for Civil Protection (BABS, formerly BZS) and is therefore especially suited to protect fixed facilities.
PLP-44041 3-phase 40A Powerline Protection PLP-44041 is a very effective EMP-Protector / Filter to protect a three phase 400/230V AC power supply with operating current up to 40A per phase. PLP-44041 combines NEMP / HEMP-protection with lightning surge protection IEC class I+II+III and an EMC filter having very high attenuation up to GHz range.For safety reasons (relatively high AC-leakage current) PLP-44041 is only suited for installations with permanent ground connection.
PLP-44041 datasheet
PLP-44101 3-phase 100A Powerline Protection
PLP-44101 is a very effective EMP-Protector / Filter to protect a three phase 400/230V AC power supply with operating current up to 100A per phase. PLP-44101 combines NEMP / HEMP-protection with lightning surge protection IEC class I+II+III and an EMC filter having very high attenuation up to GHz range.For safety reasons (relatively high AC-leakage current) PLP-44101 is only suited for installations with permanent ground connection.
PLP-44101 datasheet
PLP-44201 3-phase 200A Powerline Protection
PLP-44201 is a very effective EMP-Protector / Filter to protect a three phase 400/230V AC power supply with operating current up to 200A per phase. PLP-44201 combines NEMP / HEMP-protection with lightning surge protection IEC class I+II+III and an EMC filter having very high attenuation up to GHz range.For safety reasons (relatively high AC-leakage current) PLP-44201 is only suited for installations with permanent ground connection.
PLP-44201 datasheet
PLP-44401 3-phase 400A Powerline Protection
PLP-44401 is a very effective EMP-Protector / Filter to protect a three phase 400/230V AC power supply with operating current up to 400A per phase. PLP-44401 combines NEMP / HEMP-protection with lightning surge protection IEC class I+II+III and an EMC filter having very high attenuation up to GHz range.For safety reasons (relatively high AC-leakage current) PLP-44401 is only suited for installations with permanent ground connection. Caution: PLP-44401 is not a current compensated filter, it consists of two cases, one for L1 / L2 and one for L3 / N.
PLP-44401 datasheet
PLP-44801 3-phase 800A Powerline Protection
PLP-44801 is a very effective EMP-Protector / Filter to protect three phase 400/230V AC power with operating current up to 800A per phase. PLP-44801 combines NEMP / HEMP-protection with lightning surge protection IEC class I+II+III and an EMC filter having very high attenuation up to GHz range. For safety reasons (relatively high AC-leakage current) PLP-44801 is only suited for installations with permanent ground connection. Caution: PLP-44801 is not a current compensated filter, it consists of four cases, one for each L1, L2, L3, and N. PLP-44801 datasheet
PLP-44011 3-phase 1000A Powerline Protection PLP-44011 is a very effective EMP-Protector / Filter to protect a three phase 400/230V AC power supply with operating current up to 1000A per phase. PLP-44011 combines NEMP / HEMP-protection with lightning surge protection IEC class I+II+III and an EMC filter having very high attenuation up to GHz range.For safety reasons (relatively high AC-leakage current) PLP-44011 is only suited for installations with permanent ground connection. Caution: PLP-44011 is not a current compensated filter, it consists of four cases, one for each L1, L2, L3, and N.
PLP-44011 datasheet
USS-1 series surge protection devices are very compact and protect a single wire carrying a low voltage or signal and currents up to 0.5A.USS-1 surge protection devices are specially designed for feed-through installation into a bulkhead, e.g. directly into the metallic wall of a shielded room (Faraday's cage).Feed-through installation and high surge current capability allow simultaneous protection against lightning surges as well as HEMP / NEMP / EMP.USS-1 series products are threat-level HEMP-tested according to MIL-STD-188-125.A variety of USS-1 types are available for different applications, depending on the operating voltage.
USS-1-C is an EMP-Protector / Filter which protects one wire of an analog telephone line or signal line having only a capacitif reference to ground. USS-1-C can be used for signals up to +/-150V and currents up to 0.5A. The typical bandwidth limit is 180 kHz.If installed correctly USS-1-C works simultaneously as surge protection against NEMP / HEMP / EMP and lightning surges. USS-1-C datasheet
USS-1-6V is an EMP-Protector / Filter which protects a single wire of a signal or data line having an operating voltage up to 6V and an operating current up to 0.5A. The typical bandwidth is 300 kHz.If installed correctly USS-1-6V works simultaneously as surge protection against NEMP / HEMP / EMP and lightning surges. USS-1-6V datasheet
USS-1-12V is an EMP-Protector / Filter which protects a single wire of a signal or data line having an operating voltage up to 12V and an operating current up to 0.5A. The typical bandwidth limit is 300 kHz.If installed correctly USS-1-12V works simultaneously as surge protection against NEMP / HEMP / EMP and lightning surges. USS-1-12V datasheet
USS-1-15V is an EMP-Protector / Filter which protects a single wire of a signal or data line having an operating voltage up to 15V and an operating current up to 0.5A. The typical bandwidth limit is 300 kHz. If installed correctly USS-1-15V works simultaneously as surge protection against NEMP / HEMP / EMP and lightning surges. USS-1-15V datasheet
USS-1-24V is an EMP-Protector / Filter which protects a single wire of a signal or data line having an operating voltage up to 24V and an operating current up to 0.5A. The typical bandwidth limit is 300 kHz. If installed correctly USS-1-24V works simultaneously as surge protection against NEMP / HEMP / EMP and lightning surges. USS-1-24V datasheet
USS-1-48V is an EMP-Protector / Filter which protects a single wire of a signal or data line having an operating voltage up to 48V and an operating current up to 0.5A. The typical bandwidth limit is 300 kHz. If installed correctly USS-1-48V works simultaneously as surge protection against NEMP / HEMP / EMP and lightning surges. USS-1-48V datasheet
Meteolabor Inc. develops and produces numerous high quality Surge Protection Devices to protect the wiring of highly reliable electronics against overvoltages due to HEMP / NEMP / EMP (High altitude ElectroMagnetic Pulse) and lightning.
EMP Protection USS-1 Series: ![]() Combined lightning / HEMP / NEMP / EMP protection for a single wire of a low voltage signal line up to 0.5A |
EMP Protection USS-2 Series: ![]() Combined lightning / HEMP / NEMP / EMP protection for symmetric datalines or for single wires, depending on product type |
EMP-Protectors USN Series![]() Combined lightning and HEMP/Nemp protections for many kinds of data signals. |
EMP-Protectors USP Series ![]() Combined lightning / HEMP / NEMP / EMP protection of a DC or single or three phased AC power supply from16A up to 32A |
EMP-Protectors PLP Series![]() Combined Lightning / HEMP / NEMP / EMP protection of 3-phased AC power supplies up to 1000A per phase, for fixed installations |
EMP-Protectors CSP Series![]() Surge protection for coaxial RF-cables, different types depending on frequency range, bandwidth, RF-power, DC-bypass etc. |